How To Repair A Vertical Cement Wall
Concrete book changes due to changes in wet and temperature. Every bit concrete dries, it shrinks. Length modify related to drying shrinkage for unreinforced physical can range upward to 0.08% whereas normal reinforced concrete is about 0.02% to 0.03% due to the internal restraint associated with the reinforcing. [one]
For an unreinforced or lightly reinforced 100 ft. wall, drying shrinkage tries to shorten the wall up to about one inch. If the wall is normally reinforced, shortening is reduced to most 1/4 to 3/8 of an inch. With regards to thermal contraction, our 100 ft. wall subjected to a 50ยบF temperature drop tries to shorten an additional 5/8 of an inch.
Wall shortening from concrete drying shrinkage and/or thermal cooling combined with restraints including wall corners, intersecting walls and foundations with dowel bars causes vertical cracks to class (see figure 1). Due to shrinkage and restraints that resist wall shortening, tensile stresses form and when stresses exceed the tensile capacity of the physical, groovy occurs.
Concrete Shrinkage + Restraints = Tensile Stresses = Wall Cracks
Another way of thinking about this shrinkage and restraint beliefs is to identify our 100 ft. wall in outer space. Floating in space without restraints, the wall could freely shrink or shorten to a new length without cracking.
Dorsum on earth with wall restraints, cracks class and relieve the tensile stresses created by the concrete shrinkage. If wall stresses are non sufficiently relieved by cracking, new cracks occur between previously formed cracks. Every bit illustrated in Figure 1, most wall cracks showtime at the bottom and grow upwards due to the rigid restraint created by the foundation.
Figure 1. Typical vertical wall cracking if no joints are provided. Also, reentry corner cracks tin can form due to stress concentrations at interior corners that can contribute to vertical wall cracking.
Crack Control Options
The risk of wall swell can be reduced past minimizing the root causes. Reducing the h2o content of the concrete and/or including a shrinkage reducing admixture can help reduce the take chances of cracking or at least the severity of cracking. Concrete shrinkage is strongly dependent on the total h2o content of the concrete. So, reducing the water content, reduces concrete drying shrinkage and the risk of vertical wall cracks. If wall cracks are a concern, discuss concrete mix options to reduce drying shrinkage with your physical supplier.
Most probable, information technology will not exist possible to reduce wall restraints and concrete temperature variations. For this reason, contraction joints and horizontal reinforcing are the best options to command random vertical cracks. Of course, the designer is responsible for establishing the mix design requirements in addition to specifying either contraction joints or horizontal reinforcing or both and the related details.
Option 1. Contraction Joints
Installing contraction joints is an economic and uncomplicated way to control the location of vertical cracks. Contraction joints are weakened planes created by reducing wall thicknesses, reinforcing or both so slap-up occurs within the joints. Equally concrete dries and tensile stresses increase, cracks occur at the thinner sections inside the contraction joints.
Wrinkle joints are made using wooden, rubber, plastic, or metal strips fastened to the inside grade faces as illustrated in Effigy two. Strips create narrow vertical grooves on both sides of the wall creating thinner wall sections. Full depth of the two grooves should be at least 1/four of the wall thickness to ensure the thinner section is sufficiently weakened to command the location of cracks.
Figure 2. Details for forming contraction joints in walls.
Wall Thickness | half dozen in. | 8 in. | x in. |
A | 1 in. | 1 ane/4 in. | one three/four in.* |
B | one/2 in. | 1/2 in. | one/2 in. |
C | 3/four in. | 3/4 in. | iii/iv in. |
*May disharmonize with horizontal rebar if the wall has 2 mats
In full general, and every bit illustrated in Figure 3, recommended articulation spacing is the height of the wall for walls taller than about 12 ft. and three times the wall elevation for walls less than about 8 ft.[2] Due to wall restraints associated with corners and intersecting walls, install joints within 10 ft. to 15 ft. of wall corners and intersections. These recommendations recognize that the upper portion of the wall is probable to cool and shrink faster than the lower portion that is more restrained. Both atmospheric condition create tensile stresses within walls that create vertical cracks. Consider placing joints at abrupt wall changes, in line with openings to help command reentry corner cracks, and in locations to create an acceptable visual advent. While Figure iii illustrates wall jointing recommendations, each wall should be evaluated to determine the all-time articulation locations and spacings.
Figure 3. Recommended contraction joint locations and spacings.
Where h < 8 ft., southward = 3 x h
Where h > 12 ft., due south = h
smax = 25 ft.
Exterior grooves can exist sealed with a non-sag, elastomeric sealant (eastward.g., polyurethanes and silicones) to prevent penetration of cold air, moisture, water, and insects through cracks. Sealants tin can too be used in interior grooves to muffle cracks.
Option 2. Reinforcing
Horizontal wall reinforcing controls the width of shrinkage cracks – not the location. How tightly cracks are held together depends on the corporeality and spacing of the reinforcing. Increasing the amount or reducing the spacing of reinforcing passing through cracks, decreases crevice widths. In many cases, this is the designer's pick to control vertical wall cracks. With this design choice, don't await a crack-free wall. Expect random peachy to occur but crack widths should exist limited past the corporeality of wall (horizontal) reinforcing.
Using both load and building code requirements, designers establish the required reinforcing for walls. Horizontal reinforcing may exist determined by load conditions, minimum code requirements to ensure structural integrity, or minimum "temperature and shrinkage" reinforcing equally specified by edifice codes or the local building officials.
Kim Basham
The amount of horizontal reinforcing can be quantified by computing the reinforcing percentage that is based on the reinforcing and wall thickness. For example, #four at 12 in. on center located in the heart of an viii in. thick wall yields a reinforcing percent of 0.21%. [3] While 0.21% exceeds the minimum 0.eighteen% temperature and shrinkage reinforcing specified by the International Building Lawmaking, it may non hold the vertical wall cracks sufficiently tight to satisfy the wall'southward function or the owner's expectations.
If our example wall was 23 ft. long with 0.21% horizontal reinforcing, approximate crack widths exceeding about 0.010 in. should be expected. To limit cracks widths to about 0.010 in. and 0.004 in. (watertight), reinforcing percentages would need to be increased to approximately 0.30% and 0.55%, respectively.[4] To accomplish a 0.30% value, the reinforcing would need to be #4 at viii in. on eye and for 0.55%, #5 at 7 in. or #6 at x in. on center, respectively.
Equally shown with the simple wall example (figure three), meaning amounts of horizontal reinforcing are required to continue vertical crack widths narrow. For watertight retaining walls, the minimum wall thickness is typically ten in. with two mats of reinforcing with meaning amounts of horizontal reinforcing to go along fissure widths less than 0.004 in. Designers commonly increase the amount of horizontal reinforcing in the lower three-5 ft. of walls to help command the width of cracks that start at the bottom and grow up.
Combining Options ane & 2
Contraction joints and reinforcing can be combined to command vertical bully but if too much reinforcing crosses joints, joints may not be sufficiently weakened to activate and control the cracking location. Recommendations for reinforcing at contraction joints range from: stopping all reinforcing 2-3 in. from the joint, allowing 50% or another corporeality of the reinforcing to continue through the articulation, and discontinuing all reinforcement and installing slip dowels to maintain alignment of the adjacent wall surfaces.
A crack compactor card can assistance you determine the width of the cleft in question. Place the card on the crack and marshal the line that matches the crack width. Kim Basham
Crack Repair Options
Reducing concrete shrinkage and wall restraints and installing contraction joints with or without horizontal reinforcement does non ensure that random or out-of-joint cracks will not occur. If out-of-joint slap-up does occur, there are several repair options that can exist used to either seal or structurally repair cracks if needed.
- Route and Seal.The simplest and most economical ways to repair vertical cracks regardless of crack widths. It is a nonstructural repair that consists of routing or enlarging the crack to create a V-shaped sealant reservoir and so filling the reservoir with a non-sag, elastomeric sealant (due east.g., polyurethanes and silicones).
- Polyurethane Injection. Inject wet or leaky cracks with polyurethane resins that combine with water to course an expanding and flexible gel to asphyxiate off leaks and seal cracks. This technique is a full-depth and lasting scissure repair.
- Epoxy Injection. Welds or bonds crevice faces together and restores the soundness and integrity of the physical. However, if the injected cracks are active (still opening due to continued concrete shrinkage or acting as joints to salvage thermal stresses) new cracks may form next to the repaired cracks.
This article has presented ii proven scissure control options for walls. Unfortunately, a tertiary crack control option is oft used: let it scissure. This approach assumes you lot will deal with cracks afterwards they occur. Using this option can become time-consuming and expensive if any party misinterprets the cracks as lacking concrete or workmanship that jeopardizes the structural integrity, function, or service life of the structure. It is better to be proactive and consider crack command options and crevice expectations before starting the task.
Virtually the author
Kim Basham is president of KB Engineering, LLC which provides engineering services to the concrete industry and a registered professional person engineer in 19 states. Dr. Basham as well teaches seminars and workshops dealing with all aspects of concrete including physical technology, concrete structure, and troubleshooting for the American Concrete Institute, World of Physical, and other concrete/structure organizations. He can be reached at KBasham@KBEngLLC.com.
References
[ane] Kosmatka, S. H. and Wilson, G. L., Design and Control of Concrete Mixtures, 5th Edition, 2022, pp. 180, Portland Cement Association, world wide web.cement.org
[two] ACI 224.3R-95 Joints in Physical Construction, p. 32, American Concrete Constitute, www.concrete.org;
[3] [(0.xx in2/ft)/(viii in. x 12 in.)] 10 100 = 0.21%